Nacházíte se zde: Domovská stránka > English > Products > ZEROTESTpro
Pokročilé hledání

ZEROTESTpro

ZEROTESTpro - Loop/Line Tester

ZEROTESTpro

Features:
- Fault Loop and Line resistance and prospective fault current
- Fault Loop resistance and prospective fault current (no-trip of a RCD)
- The database (table) of fuses’ types/disconnecting times/rated currents in the memory of the ZEROTESTpro enables to evaluate  automatically the measurements results
- AC TRMS voltage 24,0 ÷ 260,0 V
- Phase (live) conductor test
- The bright multicolour OLED display
- Patent-protected storage of the test tips in transport position – sharp tips are safely hidden
- The bright LED near the test tip allows you to illuminate the measured area
- The instrument is powered by four AAA rechargeable NiMH/NiCd batteries that can be charged inside the instrument

Download manual

Fault Loop Resistance / Line Resistance (Function "~"):

 Measuring range [Ω]  0,00 - 4,99     5,0 - 49,9     50 - 200
 Operating range [Ω]  0,27 - 200
 Reference error  ± (3 % R + 5 D)*   (0,00 Ω - 4,99 Ω)
 ± (3 % R + 3 D)*   (5,0 Ω - 49,9 Ω)
 ± (3 % R)*            (50 Ω - 200 Ω)
 Operating error  ± (4 % R + 7 D)*   (0,00 Ω - 4,99 Ω)
 ± (4 % R + 4 D)*   (5,0 Ω - 49,9 Ω)
 ± (4 % R)*            (50 Ω - 200 Ω)
 Voltage range [V]  190 - 260 (48 - 52 Hz)
 Load  50 Ω, (variable no. of load pulses @ 10 ms)

Fault Loop Resistance (Function "RCD"):

 Measuring range [Ω]  0,0 - 4,9     5 - 200
 Operating range [Ω]  0,8 - 200
 Reference error  ± (5 % R + 2 D)*   (0,0 Ω - 4,9 Ω)
 ± (7 % R)*            (5 Ω - 200 Ω)
 Operating error  ± (6 % R + 2 D)*   (0,0 Ω - 4,9 Ω)
 ± (8 % R)*            (50 Ω - 200 Ω)
 Voltage range [V]  190 - 260 (48 - 52 Hz)
 Load  50 Ω, (variable no. of load pulses, variable duration)

Prospective Fault Current / Short-Circuit Current:

 Measuring range [A]  0 - 999    1,0 k - 9,9 k    10 k - 23 k
 Reference error  Take into consideration error
 of Loop/Line measurement ± 1 D
 Operating error  Take into consideration error 
 of Loop/Line measurement ± 1 D

AC voltage (TRMS value):

 Measuring range [V]  24 - 260 (48 - 52 Hz)
 Resolution [V]  0,11 
 Reference error  ± (2 % R + 2 D)*
 Operating error  ± (3 % R + 3 D)*

General:

 Power supply  4 x AAA alkaline battery 1,5 V or
 NiMH accumulator 1,2V
 Display  High contrast bright multicolour graphic OLED
 Protective class  II (double insulation)
 Over voltage class  CAT III / 300V with protective cover
 CAT  II / 300V without protective cover
 Pollution degree  2
 Degree of protection  IP 43
 Dimensions  about 260 mm x 70 mm x 40 mm
 Weight  about 0,36 kg

Included in the set: ZEROTESTpro, Twisted test lead with measuring tip, pouch, User´s Manual, Calibration Certifidate, Cardboard shipping case

Optional accessories:

 P 2011  test lead, black, 2m
 P 3011  test tip, black
 P 4011  crocodile clip, black
 P 5050  Adapter for charging accumulators
 P 5060  set of 4 NiMH AAA accumulators